Fire Resistance Classification of Multi Compartment Smoke Extraction Ducts

Each type of construction product has its own way of expressing fire performance. Through this series, we explain how to read and interpret classification codes according to the relevant European standards. Part 4 – Fire Resistance Classification of Multi Compartment Smoke Extraction Ducts Multi-compartment smoke extraction ducts are designed to extract smoke from multiple fire […]
Grafika strana1 2

Each type of construction product has its own way of expressing fire performance. Through this series, we explain how to read and interpret classification codes according to the relevant European standards.

Part 4 – Fire Resistance Classification of Multi Compartment Smoke Extraction Ducts

Multi-compartment smoke extraction ducts are designed to extract smoke from multiple fire compartments, which places specific demands on their fire resistance performance. Compared to ducts serving a single fire compartment, their behaviour under fire conditions must consider the interaction between compartments connected through the duct system.

Applicable standards

  • Testing: EN 1366-8:2024
  • Classification: EN 13501-4:2016
Designation Meaning Note
E Integrity Duct C
EI Integrity and Insulation Duct A and Duct B
ttt Classification period 30, 60, 90, 120 min
multi Smoke extraction from multiple fire compartments
ve Vertical orientation of duct
ho Horizontal orientation of duct
S Smoke leakage
p Negative pressure differential applied during the test 500, 1000, 1500 Pa,

DIAP allows pressure application from (-p) Pa up to (+500) Pa

How to read the classification

The classification distinguishes between integrity (E) and integrity with insulation (EI). These criteria define whether the duct prevents the passage of flames and hot gases (E), and additionally limits temperature increase on the unexposed side (EI), depending on the duct type.

The classification also includes the fire resistance time, expressed in minutes (e.g. 30, 60, 90, 120). This value defines the duration for which the duct meets the specified classification criteria under fire exposure.

An important element of the classification is also the orientation of the duct – vertical (ve) or horizontal (ho). The classification is only valid for the position in which the duct was tested.

Additional elements of the classification may include the smoke leakage criterion (S) and pressure conditions (p). These parameters provide further detail on the duct performance under defined test conditions, such as leakage limits and applied pressure levels.

The designation “multi” indicates that the duct is intended for smoke extraction from multiple fire compartments. This reflects the specific test setup and the resulting classification, where the duct system is assessed in conditions representing interconnected compartments.

Example

EI 120 (ho) S1500 multi

This classification describes a horizontal duct that maintains integrity and insulation for 120 minutes. The designation S1500 refers to the smoke leakage criterion verified under a pressure difference of 1500 Pa, and “multi” indicates its use for smoke extraction from multiple fire compartments.

Back to all articles
Blog

Najnovšie články

Prečítajte si najnovšie príspevky
Grafika strana1
Blog
26. 8. 2026

Fire Resistance Classification of Ventilation Ducts

Each type of construction product has its own way of expressing fire performance. Through this series, we explain how to read and interpret classification codes according to the relevant European standards. Part 1 – Fire Resistance Classification of Ventilation Ducts Applicable standards Testing: EN 1366-1:2014+A1:2020 Classification: EN 13501-3:2025 Extended application of test results: EN 15882-1:2011+A1:2017 […]
Read more
Grafika strana1 1
Blog
26. 8. 2026

Fire Resistance Classification of Fire Dampers

Each type of construction product has its own way of expressing fire performance. Through this series, we explain how to read and interpret classification codes according to the relevant European standards. Part 2 – Fire Resistance Classification of Fire Dampers Applicable standards Testing: EN 1366-2:2015 Classification: EN 13501-3:2025 Extended application of test results: EN 15882-2:2022 […]
Read more
Post14c Strana1
Blog
26. 8. 2026

Fire Resistance Classification of Single Compartment Smoke Extraction Ducts

Each type of construction product has its own way of expressing fire performance. Through this series, we explain how to read and interpret classification codes according to the relevant European standards. Part 3 – Fire Resistance Classification of Single Compartment Smoke Extraction Ducts This type of duct has a specific position within the European standardization […]
Read more
See all